machine@hongancn.comShunhao Company’s melamine crockery molding machine uses 1-on-1 circuit wiring method, that means the electrical box microcomputer input signal and the output signal has its own name, and also have their own functions and lights, so just check whether the respective signal lights are on when they are triggered, to confirm whether the electrical components are normal or damaged. The following are examples to make it clear.
Input signal:
1. Press “MOTOR START”, then No.4 light upper line of PLC should work; If not light, then check whether it is under Manual way or the button is damaged or broken off wire;
2. Take an iron bar before (Rising limited) approaching switch, then No.17 light of PLC should work; If not light, change the approaching switch or check the X17 wire broken off.
Input signal:
PLC output, because of its lower resistance - current, first start the relay and then use relay to start hydraulic valves or electromagnetic contactor.
Note: PLC lower part is LX voltage (relay coil is DC24V), R on the relay board and Y0-Y12 is AC220V. DO NOT connect “COM” with Y0-Y12.
Input signal:
1. Press
2. Connect the lower end of the PLC with a wire,
The following is a description of the input and output signals:
X0
MANUAL / AUTO
Y0
MOTOR
X1
CURING /MAUNAL FAST-DOWN SWITCH
Y1
DOWN-VALVE
X2
PATTERN SWITCH
Y2
UP - VALVE
X3
GLAZING SWITCH
Y3
MID-PRESSURE VALVE
X4
MOTOR SWITCH
Y4
HIGH -PRESSURE VALVE
X5
RETURN MOLD SWITCH
Y5
LOW-PRESSURE VALVE
X6
SECOND COLOR SWITCH
Y6
PRESSURING VALVE
X7
MANUAL FAST-UP
Y7
GUIDING RELIEF VALVE
X10
MANUAL FAST-DOWN
X11
MANUAL SLOW-UP
Y10
BACK PRESSURE MAGNETIC VALVE
X12
SLOW-DOWN LIMIT
Y11
PRE-FILL VALVE
X13
DOWN STOP LIMIT
Y12
CURING TIMING
X14
CURING SLOW-UP LIMIT
Y13
MOLDING MOVING
X15
PATTERN SLOW-UP LIMIT
Y14
BACK UP
X16
STAYING LIMIT
Y15
BACK UP
X17
UP-STOP LIMIT / EMERGENCY STOP
Y16
BACK UP
X20
Y17
BACK UP
X21
X22
X23
X24
X25
X26
X27
GLAZING SLOW-UP LIMIT
Tip:Automatic melamine molding machine with PLC system is easier to check and maintenance, WHY?
Because of this Input or Output signal from PLC will tell you which action is not proper from PLC lights showing.
When the case happening, just check the PLC lights or send pictures to us, Shunhao Engineers team could check for your machine accordingly.